3 Installation
3.6 Motor feeder
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
107
3.6.2.1 Motor cable monitoring
Pin 5 and pin 8 of the motor feeder socket are used to monitor the motor
cable's motor feeder plug and to protect the thermistor.
Monitoring is performed depending on the setting in parameter P2-27.
Figure 64:
General motor connection with motor feeder plug and motor cable monitoring
3.6.2.2 Motor cable with thermistor connection
Figure 65:
General motor connection with thermistor plug,
motor feeder plug and motor cable monitoring
The cable ends (pin 5 and pin 8) on motors with thermistors or thermostats
(Thermo-Click) must be connected in the terminal box of the motor (T1–T2).
→
For motor cable monitoring and operation without a thermistor,
the cable ends of pin 5 and pin 8 must be bridged in the terminal
box of the motor (cable monitoring T1–T2).
1
7
3
PE
M
3 ~
U
V
W
PE
≦ 20 m
(≦ 65.62 ft)
5
8
1
7
3
PE
T1
T2
M 3 ∼
ϑ
U
V
W
PE