
8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
183
P2-23
Auto Thermal
Management
AutoThermalManagement
In case of too high temperature at the heatsink, the drive
reduces the switching frequency set with P2-22 to reduce the
likelihood of an overtemperature trip.
–
0
1
0
P2-24
Start mode
Defines the behaviour of the drive relating to the enable
sensor input and also configures the automatic restart func-
tion.
0: Edge-r : Following power on or reset, the drive will not start
if a start signal (FWD/REV) is still present. To start a rising
edge is necessary.
1: Auto-0 : Following a power on or reset, the drive will auto-
matically start if a start signal (FWD/REV) is still present.
2, .., 9: Auto-1 to 9 : Following a trip, the drive will make up
to 9 attempts to restart at intervals set in P2-26. The drive
must be powered down to reset the counter. The number of
restart attempts are counted, and if the drive fails to start on
the final attempt, the drive will trip, and will require the user
to manually reset the fault.
–
0
10
0
P2-25
REAF start function
Start function after an automatic restart
0: Acceleration time (ramp)
1: Spin Start
2: According to P2-37
–
0
2
0
P2-26
Auto Reset Delay
Auto reset delay
Determines the time that will elapse between consecutive
drive reset attempts when Auto Reset is enabled in P2-24.
s
0.1
60
0.5
P2-27
Action@Thermistor-
fault Motor
Device reaction after “Thermistorfault Motor” occurs.
Possibilities device dependent
0: deactivated
1: activated
–
0
1
1
P2-28
Service Interval Time
Service Interval Time
Defines the number of operating hours, after which the
service indicator is shown on the display.
If P2-29 = 1, the counter is set to the value defined here. The
remaining time until the next service is indicated with P0-22.
h
0
60000
0
P2-29
Reset ServiceIndi-
cator
Reset Service Indicator
With P2-29 = 1 the counter for the remaining hours until the
next service is set to the value defined in P2-28. Reset of
P2-29 to 0 is done automatically.
–
0
1
0
P2-30
Parameter set
Restores factory parameter settings.
–
0
1
0
P2-31
Default selection
Default settings, country specific.
0: EU (Europe, 50-Hz networks)
1: USA (North America, 60-Hz networks)
–
0
1
0
P2-32
Access key level2
Defines the password which is used to get access to
extended parameter set (Level 2).
Access via P1-14.
–
0
65535
101
P2-33
Parameter lock
Determines whether to lock the parameters
0: OFF. All parameters can be accessed and changed
1: ON. Parameter values can be displayed, but cannot be
changed.
If a remote keypad is connected, parameters cannot be
accessed (except P1-14 and P2-33).
–
0
1
0
Parameter
Designation
Description
Unit
Min
Max
DS
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...