CHAPTER 8 - PXG200E CONFIGURATION WEB PAGE
47
EATON
PXG200E User Manual • IM02603001E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
Example - Single Main / Single Bus System
1.
System plan
- This system is a single lineup of LV switch gear. It has a
single incoming Main from the utility that has an Eaton IQ230M meter
monitoring the power consumption at COM1 (Modbus RTU) address 01.
The current capacity of the Main feed is 1000A.
There are four feeder circuits connected to the power Bus coming from
the Main. Each of these circuits is monitored by an Eaton IQ230M meter
at COM1 (Modbus RTU) address 02 through 05. Each feeder circuit has a
capacity of 100A. The feeder circuits are to be labeled Feeder 1-4.
The system is depicted in
.
Figure 39
LV Source 1 with IQ230M meter
Capacity - 1000A - COM1 Addr01
Capacity - 100A
Meter IQ230M
COM1 Addr02
Feeder 1
Capacity - 100A
Meter IQ230M
COM1 Addr03
Feeder 2
Capacity - 100A
Meter IQ230M
COM1 Addr04
Feeder 3
Capacity - 100A
Meter IQ230M
COM1 Addr05
Feeder 4
PXG200E_031
Power Bus 1
Main from Utility
RETURN