CHAPTER 8 - PXG200E CONFIGURATION WEB PAGE
EATON
PXG200E User Manual • IM02603001E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
46
Adding Downstream Devices
Downstream devices are added to the PXG200E using the device list editor.
As you add devices to the device list, you will also enter information that
allows the web page views served by your PXG200E to be automatically
generated.
Mains, Buses and Devices
The device list editor uses these three objects to help you organize your
system view.
A
Main
represents a primary electrical feed entering the facility or
equipment. A Main can be:
•
Unmonitored
•
Monitored by a meter
A
Bus
represents a group of devices. It will often be used to indicate a group
of electrical monitoring devices connected to the same power Bus.
Devices
are the actual communicating units that are connected to one of
the downstream communications ports of the PXG200E.
Recommended Procedure
The following procedure is recommended to configure the device list of the
PXG200E:
1.
Plan your system – The following information will be required as you set
up the PXG200E device list:
a.
Mains and Buses you would like to define for your system
b.
Current capacity of monitored circuits (optional)
c.
List of downstream devices (i.e. IQ230M) and their downstream port
addresses
d.
Names you want to assign to the devices, Mains and Buses
2.
Enter Mains
3.
Enter Buses
4.
Add Devices to Buses
NOTICE: Based on the number of devices being added, a scrollbar
may appear on the right side of the PXG screen. The user can scroll
up or down to view all of the devices installed on the system.
RETURN