For more information visit:
www.EatonElectrical.com
Inside EZD
MN05013005E
398
QA analog output
The analog output operates with decimal values between 0
and 1023. This corresponds to a 10-bit resolution. At the
output this corresponds to a physical voltage between 0 V and
10 V DC.
Negative values such as: –512 are evaluated as zero and
output as 0 V DC.
Positive values greater than 1023, such as: 2047, are
evaluated as 1023 and output as 10 V DC.
Loading and saving
programs
You can either use the EZD interface to save programs to a
memory card or use EZSoft and a transmission cable to
transfer them to a PC.
EZD without display and keypad
EZD models without buttons and a display can be loaded with
the EZD program via EZSoft or automatically from the fitted
memory card every time the power supply is switched on.