For more information visit:
www.EatonElectrical.com
Programming wiring
MN05013005E
176
Parameters of BT01 function block:
Source range:
>I1 MB15
Destination range:
>I2 64
Number of bytes:
>NO
4
Marker MB01: 1
After a rising edge from 0 to 1 at coil BT01T_ the value 45 is
present in the marker bytes MB65 to MB68.
Example:
Initialization of marker blocks, definition of a range in a
different format.
The value of marker byte MB60 is to be transferred to MD80
and MD81.
Parameters of BT01 function block:
Source range:
>I1 MB60
Destination range:
>I2 MD80
Number of bytes:
>NO
8
J
Destination range: Constant 64:
Marker MB01 plus Offset: 1 + 64 = 65
J
MB65.
Source range
Value of source
marker range
(decimal)
Destination
range
Value of
destination
marker range
(decimal)
MB15
45
MB65
45
MB66
45
MB67
45
MB68
45
J
The transfer is in byte format. MD80 has 4 bytes and MD81
has 4 bytes, which means that
<NO
has the value 8.