Configuration of the EZ-NET network
For more information visit:
www.EatonElectrical.com
MN05013005E
343
The standard settings for the input and output devices are:
Station number (EZ-NET-ID) and baud rate can be specified
via station 1.
Station message types
The EZ-NET network recognizes various message types.
They are:
• Output data of station 1 (Q., S.) which is sent to stations
without programs.
• Network outputs and inputs sent and received between
stations with programs (*SN, *RN).
• Data sent and received via the network between stations
with programs (PT and GT function blocks).
• Inputs, outputs, station status (I, R, Q, S) transfers.
• Loading programs to and from every station.
The EZ-NET network is based on a CAN (Controller Area
Network) system. Each message type has its own ID. The
message priority is determined via the respective ID. This is
important in transmission borderline cases to ensure that all
messages reach their destination.
Transfer behavior
Network CPU data transfer to program image
The EZD network connection is equipped with its own CPU.
Network data can therefore be processed while the program
is running. After each program cycle, the status of the network
SEND IO
å
REMOTE RUN å
REMOTE IO
å