Function blocks
For more information visit:
www.EatonElectrical.com
MN05013005E
239
Power flow display
Jumped ranges are indicated by the coils in the power flow
display.
All coils after the jump coil are shown with the symbol of the
jump coil.
Example
A selector switch allows two different operations to be set.
• Sequence 1: Switch on Motor 1 immediately.
• Sequence 2: Switch on Guard 2, Wait time, then switch
on Motor 1.
Contacts and relays used:
• I1 Sequence 1
• I2 Sequence 2
• I3 Guard 2 moved out
• I12 Motor-protective circuit-breaker switched on
• Q1 Motor 1
• Q2 Guard 2
•
T 01
Wait time 30.00 s, on-delayed
•
D 01
Text “motor-protective circuit-breaker tripped”
Attention!
If rungs are skipped, the states of the coils are retained. The
time value of timing relays that have been started will
continue to run.