FP-5000
IL17569C
Page 4-15
Effective Date: 12/05
Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 4-15
“Power Factor” Display:
“Zone Interlocking” Display:
Power Factor
55A Apparent PF
55D Displacement PF
55A Apparent PF
Trigger PF: Disable
Reset PF: Disable
Delay (s): 0
55D Displacement PF
Trigger PF: Disable
Resent PF: Disable
Delay (s): 0
“Sync-Check” Display:
Synch-Check
25 Synch-Check
Hot/Dead Vol Def
25 In-Sync Characteristic
Synch Override
Other Settings
25 Synch-Check
Function: Disable
Max BCT (c): 3
Synch Timeout: 1800
Hot/Dead Vol Def
Min Live Voltgage: 65
Max Dead Voltgage: 3
Volt Dead Time: 10
Other Settings
Line Phase: A
Ext Bypass: Disable
Sync Block: Disable
25 In-Sync Characteristic
Max Voltgage Diff: 24
Max Angle Diff: 20
Max Slip Diff: 0.20
Synch Override
DBDL: Disable
DBHL: Disable
LBDL: Disable
Zone Interlocking
Zone Interlock Trip
Zone Interlock Out
Zone Interlock Trip
Phase or Ground: Disable
Direction: Both
Zone Interlock Out
Phase or Ground: Disable
Direction: Both