25 Synch-Check
Synch-Check Settings
Function:
Select to supervise closing
operation
Disable, enable
Disable
Max BCT (c):
Maximum breaker close time delay 0 to 9999 cycles
(1 cycle increments)
3
Synch Timout:
Synch-Check failure timer
0 to 65535 cycles
(1 cycle increments)
1800
Hot/Dead Vol Def
Minimum & Maximum Live & Dead
Voltgage Settings
Min Live Voltage:
Minimum live voltage
10 to 250 Volts
(Increments of 1)
65
Max Dead
Voltage:
Maximum dead voltage
1 to 150 Volts
(Increments of 1)
3
Volt Dead Time:
Voltage dead time
0 to 9999 cycles
(1 cycle increments)
10
25 In-Synch
Characteristic
Voltage , Angle & Slip Difference
Settings
Max Voltage Diff:
Maximum voltage across breaker
allowed when closing
1 to 100 Volts
(Increments of 1)
24
Max Angle Diff:
Maximum angle difference allowed
when closing
1 to 60 degrees
(Increments of 1)
20
Max Slip Diff:
Maximum slip difference allowed
when closing
1 to 2.00 Hz
(Increments of 1)
0.20
Synch Override
Synch-Check Override Settings
DBDL:
Dead bus and dead line
Disable, enable
Disable
DBHL:
Dead bus and hot line
Disable, enable
Disable
LBDL:
Live bus and dead line
Disable, enable
Disable
Other Settings
Other Synch-Check Settings
Line Phase:
Line voltage phase for Synch
checking
A, B, C, AB, BC, CA
A
Ext Bypass:
External by-pass using contact input Disable, enable
Disable
Synch Block:
Select to block Synch-check function
using contact input
Disable, enable
Disable
5.5.2.11
5.5.2.11
Synch-Check Function: Select Synch-check, minimum live voltage, characteristics and override device settings (25)
5.5.2.11
5.5.2.11
5.5.2.11
seconds
(1 second increments)