FP-5000
IL17569C
Page 4-9
Effective Date: 12/05
Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 4-9
Min <Variable>
(Variable)
Magnitude
Date
mm/dd/yy
Time
hh:mm:ss
The minimum values for each of the above parameters is compared
to the last minimum value for that parameter every 32 cycles. If the
new value is less than the last minimum, the value is updated. Power
Factor Minimum is the most leading power factor value measured.
4.6.1.5 Selecting the “Minimum” Sub-menu
This menu allows the user to view the following system parameters.
(See
Display 4.8
Minimum Sub-menu.)
• Minimum currents (IA, IB, IC, IX, IR)
• Minimum L-L Voltages (VAB, VBC, VCA)
• Minimum L-N Voltages (VA, VB, VC)
• Minimum Power (Watt, Var, VA)
• Minimum Frequency
• Minimum Power Factor (Apparent, Displacement)
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurrence.
Display 4.8 Minimum Sub-menu
Min Rst Date & Time
Date
mm/dd/yy
Time
hh:mm:ss
4.6.1.6 Selecting the “Maximum” Sub-menu
This menu allows the user to view the following system
parameters. (See
Display 4.9
Maximum Sub-menu.)
• Maximum currents (IA, IB, IC, IX, IR)
• Maximum L-L Voltages (VAB, VBC, VCA)
• Maximum L-N Voltages (VA, VB, VC)
• Maximum Power (Watt, Var, VA)
• Maximum Frequency
• Maximum Power Factor (Apparent, Displacement)
• Maximum Reset Date & Time
Max <Variable>
(Variable)
Magnitude
Date
mm/dd/yy
Time
hh:mm:ss
Min Rst Date & Time
Date
mm/dd/yy
Time
hh:mm:ss
Table 4.3 Maximum Sub-menu
Where <Variable> (Variable) =
<IA Current>
(IA)
<IB Current>
(IB)
<IC Current>
(IC)
<IX Current>
(IX)
<IR Current>
(IR)
<VAB Voltage>
(VAB)
<VBC Voltage>
(VBC)
<VCA Voltage>
(VCA)
<VA Voltage>
(VA)
<VB Voltage>
(VB)
<VC Voltage>
(VC)
<System Watts>
(MWatts)
<System Vars>
(MVAR)
<System VA>
(MVA)
<Frequency>
(Freq)
<Apparent PF>
(Apt PF)
<Displacement PF>
(DisP PF)
Display 4.9 Maximum Sub-menu
The Date and Time Stamp is also recorded on the same page with
the minimum value display for each parameter occurrence.
The maximum values for each of the above parameters is compared
to the last maximum value for that parameter every 32 cycles. If the
new value is greater than the last maximum, the value is updated.
Power Factor Maximum is the most lagging power factor value
measured.
Table 4.2 Minimum Sub-menu
Where <Variable> (Variable) =
<IA Current>
(IA)
<IB Current>
(IB)
<IC Current>
(IC)
<IX Current>
(IX)
<IR Current>
(IR)
<VAB Voltage>
(VAB)
<VBC Voltage>
(VBC)
<VCA Voltage>
(VCA)
<VA Voltage>
(VA)
<VB Voltage>
(VB)
<VC Voltage>
(VC)
<System Watts>
(MWatts)
<System Vars>
(MVAR)
<System VA>
(MVA)
<Frequency>
(Freq)
<Apparent PF>
(Apt PF)
<Displacement PF>
(Disp PF)