FP-5000
IL17569C
Page 4-19
Effective Date: 12/05
Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 4-19
“Output Relay CFG”
Display:
4.6.2.5 Output Relay
CFG
Output Trip1
Monitor: On
Function: OR
Dropout: Off Delay
Off Delay (c): 5
IN1: Trip AllProt
IN2: Control Open Bkr
IN3: Unused
IN4: Unused
Output Rly4
Function: Disable
Dropout: Unlatched
Off Delay (c): 0
IN1: Unused
IN2: Unused
IN3: Unused
IN4: Unused
Output Trip 3
Function: OR
Dropout: Latched
Off Delay (c): 0
IN1: Trip BF
IN2: Unused
IN3: Unused
IN4: Unused
Output Trip2
Monitor: Off
Function: Disable
Dropout: Unlatched
Off Delay (c): 5
IN1: Unused
IN2: Unused
IN3: Unused
IN4: Unused
Output Rly5
Function: OR
Dropout: Off Delay
Off Delay (c): 10
IN1: Control Close BK
IN2: Unused
IN3: Unused
IN4: Unused
Output Relay CFG
Output Trip1
Output Trip2
Output Rly3
Output Rly4
Output Rly5
Output Alarm
Output Aux LED
Trip Indicator
Alarm Indicator
Pickup Indicator
Output Alarm
Function: OR
Dropout: Unlatched
Off Delay (c): 0
IN1: Trip AllProt
IN2: Trip All Alm
IN3: Sys Alm All Alm
IN4: Contrl All Alm
Alarm Indicator
Dropout: Latched
Trip1: Disable
Trip2: Disable
Rly3: Disable
Rly4: Disable
Rly5: Disable
Alarm: Enable
Rly Healthy: Enable
Output Aux LED
Function: OR
IN1: Unused
IN2: Unused
IN3: Unused
IN4: Unused
Pickup Indicator
Dropout: Unlatched
IOC: Enable
TOC: Enable
Volt: Enable
OverFreq: Enable
UnderFreq: Enable
Unbalance: Enable
Prot Alarm: Disable
Power Prot: Disable
Trip Indicator
Dropout: Latched
Trip1: Enable
Trip2: Enable
Rly3: Disable
Rly4: Disable
Rly5: Disable
Alarm: Disable
Rly Healthy: Disable