Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 5-37
FP-5000
IL17569C
Page 5-37
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
Block Ir IOC
Block Residual Instantaneous
Overcurrent Settings
50R-1
Select to block the residual
overcurrent 1 while in cold load
condition
Yes, No
Yes
50R-2
Select to block the residual
overcurrent 2 while in cold load
condition
Yes, No
Yes
50R-3
Select to block the residual
overcurrent 3 while in cold load
condition
Yes, No
Yes
Block Ph IOC
Block Phase Instantaneous
Overcurrent Settings
50P-1
Select to block the phase
instantaneous overcurrent 1 while
in Cold load condition
Yes, No
Yes
50P-2
Select to block the phase
instantaneous overcurrent 2 while
in Cold load condition
Yes, No
Yes
50P-3
Select to block the phase
instantaneous overcurrent 3 while
in Cold load condition
Yes, No
Yes
Block I Unbal (46)
Block Current Unbalance Settings
46-1
Select to block current unbalance 1
while in cold load condition
Yes, No
Yes
46-2
Select to block current unbalance 2
while in cold load condition
Yes, No
Yes
Block Power 32
Block Power Settings
32-1
Select to block power 1 while in cold
load condition
Yes, No
Yes
32-2
Select to block power 2 while in cold
load condition
Yes, No
Yes
32-3
Select to block power 3 while in cold
load condition
Yes, No
Yes
Cold Load Pickup:
cont.
5.5.8
5.5.8
5.5.8
5.5.8