Effective Date: 12/05
For more information visit:
www.eatonelectrical.com
Page 5-21
FP-5000
IL17569C
Page 5-21
Effective Date: 12/05
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
Output Trip1
Output Trip 1 Relay Settings
Monitor:
Select "Breaker Trip" coil circuit
monitoring to on or off
Off, On
ON
Function:
Select logic output function for
Output Trip1
OR, AND, NOR, NAND,
disable
OR
Dropout:
Select relay state after trip occurs
Latched, unlatched, off delay Off Delay
Off Delay (c):
select delay for Trip Relay to
dropout after trip event clears
1
0 to 600 cycles
(1 cycle increments)
5
IN1:
Select logic input IN1 for Output
Trip1
*See Logic Input Options
Table 5.10
Trip AllProt
IN2:
Select logic input IN2 for Output
Trip1
*See Logic Input Options
Table 5.10
Cntrl,
OpenBkr
IN3:
Select logic input IN3 for Output
Trip1
*See Logic Input Options
Table 5.10
Unused
IN4:
Select logic input IN4 for Output
Trip1
*See Logic Input Options
Table 5.10
Unused
Output Trip2
Output Trip2 Relay Settings
Monitor:
Select "Close" coil circuit monitoring
to on or off
Off, On
Off
Function:
Select logic output function for
Output Trip2
OR, AND, NOR, NAND,
disable
Disable
Dropout:
Select relay state after trip occurs
Latched, unlatched, off delay Unlatched
Off Delay (c):
select delay for Trip2 Relay to
dropout after trip event clears
1
0 to 600 cycles
(1 cycle increments)
0
IN1:
Select logic input IN1 for Output
Trip2
*See Logic Input Options
Table 5.10
Unused
IN2:
Select logic input IN2 for Output
Trip2
*See Logic Input Options
Table 5.10
Unused
IN3:
Select logic input IN3 for Output
Trip2
*See Logic Input Options
Table 5.10
Unused
IN4:
Select logic input IN4 for Output
Trip2
*See Logic Input Options
Table 5.10
Unused
Output Configuration Settings:
Phase time overcurrent (51P) and instantanious (50P-1 & 50P-2) device settings
5.5.6
9.2
9.6
5.5.6
9.2
9.6
1
This setting is only used if the “Dropout” setting is set to “Off Delay.”
Note:
The I/O Configuration Setting in the System Configuration settings menu must be set to “custom” for these
set points to be configured. Otherwise the default settings displayed are used. See sections 5.4.5 and 5.4.6 for
details.
Table 5.6 Output Configuration Settings