background image

1

60-2481—2

J.H.  •  Rev. 10-94  •  ©Honeywell Inc. 1994  •  Form Number 60-2481—2

R182J, R482J, R845A, R847A,

R882J, RA89A, RA832A

Switching Relays

These relays provide intermediate or heavy

duty service in a wide variety of switching con-
figurations.

Relays with 24V control coils: Rl82J, R882J, R847A,
RA89A, RA832A, and R845A.

Relays with line voltage control coils: R482J.

Relays with internal 24V transformer: R182J,
RA89A, RA832A, R845A, and R847A.

Relays for use with an external 24V supply: R882J.

Heavy duty relays: R847J.

R847A has flexible internal leads to provide either
spst or spdt switching.

RA832A has contacts for low voltage and
millivoltage (Powerpile

®

) use.

CONTENTS

Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 3
Service and Checkout ..................................... 6

Содержание R182J

Страница 1: ...l82J R882J R847A RA89A RA832A and R845A Relays with line voltage control coils R482J Relays with internal 24V transformer R182J RA89A RA832A R845A and R847A Relays for use with an external 24V supply R882J Heavy duty relays R847J R847A has flexible internal leads to provide either spst or spdt switching RA832A has contacts for low voltage and millivoltage Powerpile use CONTENTS Specifications 2 Or...

Страница 2: ...240 3 7 22 2 R482J Controlled by a line 120 2 wire 120 0 08 7 4 44 4 voltage controller 208 240 208 240 0 04 3 7 22 2 R845A For hot water zone control systems or spst control of two separate loads 120 Dpst 24 0 40 7 4 44 4 R847A Provides switching for 120 22 100 high current loads such as cooling compressors 240 10 50 R882J For use with separate low voltage power source 24 Dpdt 7 4 44 4 RA89A For ...

Страница 3: ... 1 35 M3823 2 75 15 16 WHEN INSTALLING THIS PRODUCT 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instruc...

Страница 4: ...must not exceed the relay load rating Fig 11 is an internal view of the RA832A showing terminal locations and barriers Never connect load terminals to a load that takes more current than the amount listed in the electrical ratings on the relay See Table 3 for wiring length specifications Fig 2 Internal schematic and typical hookup for RA89A TABLE 3 WIRE LENGTH SPECIFICATIONS Fig 3 Internal schemat...

Страница 5: ... 1 1 TO POWER LOW VOLTAGE CLASS 2 2 WIRE THERMOSTAT R845A POWER SUPPLY PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED WHEN CONTROLLING TWO LOADS USE 3 AND 4 FOR LINE VOLTAGE LOAD AND 5 AND 6 FOR LINE OR LOW VOLTAGE LOAD IF USING LOW VOLTAGE USE A SEPARATE TRANSFORMER 2 M3820 6 5 LOAD 1 TO POWER LOAD 2 1 1 2 3 3 W W R R B W R B B X R182J W R B X R182J W R B X R182J THREE WIRE LOW VOLT...

Страница 6: ...82J 3 3 R882J N O N C N C 5 3 7 6 N O 4 2 1 8 M8235 CONTROLLER LOAD LOAD COM COM LOW VOLTAGE SOURCE Service and Checkout 1 Never use oil on any part of the relay coil or contacts 2 Keep the cover on the relay during normal operation and remove only for service and checkout 3 Relay contacts require no cleaning contacts close with a wiping action and are self cleaning They may turn black after being...

Отзывы: