Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
81U-1 Underfreq
Underfrequency Settings
Threshold:
Select frequency threshold
45 to 65, disable
(0.01 Hz increments)
Disable
Delay (c):
Select delay time, which is based
on power system frequency
0 to 9999
(1 cycle increments)
60.00
81O-1 Overfreq
Overfrequency Settings
Threshold:
Select frequency threshold
45 to 65, disable
(0.01 Hz increments)
Disable
Delay (c):
Select delay time, which is based
on power system frequency
0 to 9999
(1 cycle increments)
60
Freq Protection:
Selects underfrequency (81U-1) and overfrequency (81O-1) device settings
5.5.2.7
8.8
5.5.2.7
8.8
Display Setting
Description
Setpoint Range/
Value Selection
Default
Setting
Selected
Value
Refer to
Sec. #
32-1 Pwr
Definition
Power Protection Settings 1
Direction:
Select the direction of power
Forward, Reverse, Both
Reverse
Criterion:
Select if the threshold is based on
over or under power
Over, Under
Over
32-1 Pwr Trip
Threshold:
Select the magnitude of the power
required
0.02 to 4.00
pu
* or Disable
Disable
Delay (c):
Select delay time in cycles
0 to 65535 cycles
(1 cycle increments)
10
32-2 Pwr
Definition
Power Protection Settings 2
Direction:
Select the direction of power
Forward, Reverse, Both
Reverse
Criterion:
Select if the threshold is based on
over or under power
Over, Under
Over
32-2 Pwr Trip
Power Trip Settings
Threshold:
Select the magnitude of the power
required
0.02 to 4.00
pu
* or Disable
Disable
Delay (c):
Select delay time in cycles
0 to 65535 cycles
(1 cycle increments)
1
* 1pu = 3 x CT secondary rating x VT secondary rating for wye; the square root of 3 x VT secondary rating x CT secondary
rating for delta
5.5.2.6
Power Protection:
Select power protection and trip settings (32-1 & 32-2)
5.5.2.6
5.5.2.6
5.5.2.6