MPR500 Motor Protection Relay User's Guide

Brief Overview

a
b
c

d

e

f

g

h

a  –   Run LED

b  –   Trip/Pickup LED

c  –   Thermal LED

d  –   Down key

e  –   Up key

f   –   Reset/Mode key

g  –   Test key

h  –   Data LED

i   –   Function LED

1. General Description

MPR500  is  a  motor  protection  relay  that  combines 

thermal overload, short circuit, undercurrent, unbalance, 

phase  loss,  phase  sequence,  lock/stall  rotor  and  earth 

fault protections.

MPR500  incorporates  a  4-digit  LED  indicator  which 

allows  direct  numerical  readout  of  set  values,  actual 

measured value and system indication.

MPR500  has  2  relay  outputs  (R1  and  R2).  R1  is  On 

under normal operating condition to allow motor running, 

and off during tripping. R2 is programmable to give signal 

in various conditions.

A  programmable  binary  input  is  provided  to  perform 

various operations upon binary input triggering.

2. Display

2.1 Current and Thermal Capacity Display

During  power  up,  when  the  relay  is  not  under  tripping 

condition,  the  display  shows  current    in  ampere  or 

thermal  capacity  %.  The  Function  LED  indicates  which 

parameter  is  being  displayed.  The  Data  LED  showing 

value. 

Press “UP” or “DOWN” to scroll through the parameters.

1

       

Motor Protection Relay

t  >>

I <<
t <<

6X

Start

o

  >>

o

  >>

CT

Stall

B

 

t

SW

I >>

S

 >>

i

Symbols

t

6X    

– 

Thermal overload time constant

I>>   – Short circuit/High set Overcurrent
t>>   – Short circuit/High set Overcurrent 

           delay time
I<     – Undercurrent
t<     – Undercurrent delay time
        – 

Unbalance

t       – 

Unbalance delay time

I

0

>   – Earth fault

t

0

>   – Earth fault delay time

I

S

>> – Prolonged starting/stall rotor

t

Start  

– 

Prolonged starting delay time

t

Stall  

– 

Stall rotor delay time

I

B       

– Base/full load current

CT   – External current transformer ratio
SW  – Soft switch 

I

L1

I

L2

I

L3

I

0

Thermal

Figure 1: Front panel overview

Figure 2: Current and thermal capacity display

For  current  more  than  1000A,  a  dot  is  shown  behind 

least significant digit. Eg: 

1.25.

 = 1.25kA

I

L1

 - Phase 1 current

I

L2

 - Phase 2 current

I

L3

 - Phase 3 current

I

0

 - Zero sequence/Earth fault current

Thermal % - Thermal capacity % (Thermal

 

overload trip-

ping at 100%)

During Thermal capacity display, thermal capacity can be 

cleared to 0% by pressing "UP" and "DOWN" simultane-
ously for longer than 1.5 seconds.

 

Warning:  Clearing  thermal  capacity  effectively  reset 
to  cold  start  condition,  user  is  not  encouraged  to 
clear thermal capacity unless it is sure that motor is 
cool enough to run/start within its thermal limit.

V1.3

Summary of Contents for MPR500

Page 1: ...showing value Press UP or DOWN to scroll through the parameters 1 Motor Protection Relay t I t t6X tStart Io to CT tStall IB t SW I IS i Symbols t6X Thermal overload time constant I Short circuit High...

Page 2: ...Settings and Protection Features 3 1 Setting Display When the relay is not under tripping condition pressing RESET MODE will scroll through various settings Function LED showing number or alphabet to...

Page 3: ...me 0 25s In steps of 0 1s for 0 10s in steps of 1s for 10 25s Delay time for phase unbalance 8 I0 Earth fault off 10 60 of IB In steps of 1 Earth fault setting in of IB 9 t0 Earth fault delay time 0 2...

Page 4: ...s the maximum period of time when motor current is allowed to reach a 6 x IB Cooling constant time is defined as 4 times of heating constant time and is applicable when motor current is less than 0 2...

Page 5: ...than specified 3 2 10 Earth Fault Earth fault protection is based on zero sequence current calculation Tripping takes place when the current is larger than earth fault setting in of IB for longer than...

Page 6: ...Current Thermal display press RESET MODE to jump to Tripping History Display Display shows the previous tripping status with a dot blinking at Function LED To clear tripping history press UP and DOWN...

Page 7: ...ront 1 40s In steps of 0 1s for 1 10s in steps of 1s for 10 40s off 2 12 x IB In steps of 1 x IB 0 25s In steps of 0 1s for 1 10s in steps of 1s for 10 25s off 20 90 of IB In steps of 1 0 60s In steps...

Reviews: