Installation Guide
ECL Comfort 210 / 310, application A214 / A314
2.5 Electrical connections
2.5.1 Electrical connections 230 V a.c. in general
Safety Note
Necessary assembly, start-up, and maintenance work must be
performed by qualified and authorized personnel only.
Local legislations must be respected. This comprises also cable size
and isolation (reinforced type).
A fuse for the ECL Comfort installation is max. 10 A typically.
The ambient temperature range for the ECL Comfort in operation is
0 - 55 °C. Exceeding this temperature range can result in malfunctions.
Installation must be avoided if there is a risk for condensation (dew).
The common ground terminal is used for connection of relevant
components (pumps, motorized control valves).
Factory established jumpers in the base part:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
See also the A214 Mounting Guide (delivered with the application key)
for application specific connections.
Electrical connections, 230 V a.c., power supply, pumps, dampers,
motorized control valves etc.
Connections, in general:
See also the A214 Mounting Guide (delivered with the application key)
for application specific connections.
62
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy