Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Adapt. time (adaptation time)
1x061
Circuit
Setting range
Factory setting
All
*
*
Controls how fast the compensation temperature influences the desired
flow / duct temperature.
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired flow / duct temperature is adapted quickly.
Major
value:
The desired flow / duct temperature is adapted slowly.
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Infl. - max. (compensation temp., 1. point)
1x062
Circuit
Setting range
Factory setting
All
*
*
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is higher than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets above the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets above the set limit.
Example
The limit value is set to 5 °C.
‘Infl. max.’ is set to -1.5.
The actual compensation temperature is 7°C (2 degrees above the
limit value).
Result:
The desired flow / duct temperature is changed by -1.5 x 2 = -3.0
degrees.
MENU > Settings > Compensation 1
MENU > Settings > Surface limit
Infl. - min. (compensation temp., 1. point)
1x063
Circuit
Setting range
Factory setting
All
*
*
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is lower than the set limit.
* See Appendix “Parameter ID overview”
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets below the set limit.
Example
The limit value is set to 5 °C.
‘Infl. min.’ is set to 2.5.
The actual compensation temperature is 2°C (3 degrees below the
limit value).
Result:
The desired flow / duct temperature is changed by 2.5 x 3 = 7.5
degrees.