Installation Guide
ECL Comfort 210 / 310, application A214 / A314
ID
Parameter Name
A214.x
A314.x
Setting range
Factory
Unit
Own settings
11168
Max. Pressure
4, 6
0 ... 1999
400
pascal
11169
Min. Pressure
4, 6
0 ... 1999
50
pascal
11174
Motor pr.
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
OFF, 10 ... 59
OFF
Min
11177
Temp. min.
1
-20 ... 110
5
°C
-||-
2, 3, 4, 5, 6
1, 2, 3
5 ... 150
10
°C
-||-
4, 5, 6, 7, 9
5 ... 150
15
°C
11178
Temp. max.
1
-20 ... 110
40
°C
-||-
2, 3, 4, 5, 6
1, 2, 3
5 ... 150
40
°C
-||-
4, 5, 6, 7, 9
5 ... 150
35
°C
11179
Summer, cut-out
4, 5
OFF, 1 ... 50
OFF
°C
11182
Infl. - max.
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7
-30.0 ... 0.0
-2.0
-||-
9
-30.0 ... 0.0
0.0
11183
Infl. - min.
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7
0.0 ... 30.0
2.0
-||-
9
0.0 ... 30.0
0.0
11184
Xp
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
5 ... 250
80
K
11185
Tn
1, 2, 3, 4, 5, 6
1, 2, 3, 5, 6, 7, 9
1 ... 999
30
Sec
-||-
4
1 ... 999
100
Sec
11186
M run
1, 2, 3, 4, 5, 6
1, 2, 3, 5, 6, 7, 9
5 ... 250
30
Sec
-||-
4
5 ... 250
35
Sec
11187
Nz
1, 2, 3, 4, 5, 6
1, 2, 3
1 ... 9
3
K
-||-
4
0 ... 9
1
K
-||-
5, 6, 7, 9
0 ... 9
2
K
11189
Min. act. time
1, 2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
2 ... 50
3
11194
Stop difference
6
0.5 ... 9.0
1.0
K
-||-
4, 5, 6, 7
1 ... 15
3
K
11301
High T max Y2
3
0.0 ... 75.0
25.0
m/s
11303
Low T max Y1
3
0.0 ... 75.0
5.0
m/s
11368
1. step level
4, 5, 6, 7
5 ... 95
80
%
11369
2. step level
4, 5, 6, 7
5 ... 95
85
%
11500
Send desired T
1, 2, 3, 4, 5, 6
1, 2, 3
OFF ; ON
ON
11609
Low Y
3
0.0 ... 10.0
2.0
V
11610
High Y
3
0.0 ... 10.0
10.0
V
11616
Alarm value
2, 3, 4, 5, 6
1, 2, 3
0 ... 1
0
-||-
4, 5, 6, 7, 9
0 ... 1
1
11617
Alarm time-out
2, 3, 4, 5, 6
1, 2, 3
0 ... 240
0
Sec
-||-
4, 5, 6, 7, 9
0 ... 240
10
Sec
11623
Digital
1, 2, 3, 4, 5, 6
1, 2
OFF ; ON
OFF
11636
Alarm value
1, 2, 3, 4, 5, 6
1, 2, 3
0 ... 1
0
-||-
4, 5, 6, 7, 9
0 ... 1
1
11637
Alarm time-out
1, 2, 3, 4, 5, 6
1, 2, 3
0 ... 240
0
Sec
-||-
4, 5, 6, 7, 9
0 ... 240
10
Sec