Installation Guide
ECL Comfort 210 / 310, application A214 / A314
5.2 Flow temperature / Inlet temperature
The temperature, measured by S3, can be a flow or an air duct
temperature.
The desired temperature at S3 in the subtypes A214.1 - A214.6 and
A314.1 - A314.3 is indicated as 'Desired balance T'.
The desired temperature at S3 in the subtypes A314.4 - A314.7 and
A314.9 is indicated as 'Desired T comfort' / 'Desired T saving'.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Flow temperature
Desired balance T
1x008
Circuit
Setting range
Factory setting
All
*
*
* See Appendix “Parameter ID overview”
Set the desired temperature at S3.
In all applications, the S3 temperature sensor is the most important
sensor and must always be connected.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Dead zone
1x009
Circuit
Setting range
Factory setting
All
*
*
When the application runs in combined heating / cooling mode or as
2-stage heating, the desired duct or room temperature is increased with the
dead zone value when in cooling mode.
This setting prevents unexpected changes (instability) between heating
and cooling operation.
* See Appendix “Parameter ID overview”
OFF:
No dead zone between heating and cooling
operation or 2-stage heating.
Value:
The number of degrees between the desired
duct or room temperature in heating mode and
the desired duct or room temperature in cooling
mode.
Duct / room temp.
Dead zone
Desired temp.,
cooling
Desired temp.,
heating
Heating
°
C
Cooling
Actual
Dampened
Example
Desired duct / room temperature: 20 °C
Dead zone:
5 K
When the duct / room temperature rises above 20 °C, heating stops.
When the duct / room temperature rises above 25 °C, cooling starts.
When the duct / room tempeture falls below 25 °C, cooling stops.
When the duct / room tempeture falls below 20 °C, heating starts.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
117