Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
Accum. filter (Accummulation filter)
1x082
Circuit
Setting range
Factory setting
All
*
*
The value determines the filtering of the desired flow / duct temperature in
order to change correctly from heating to cooling mode or vice versa.
The set value is an indirect time constant. The resulting time constant is
listed in the examples below.
* See Appendix “Parameter ID overview”
Low value:
Minor dampening.
High value:
Major dampening.
The setting values (examples) give the following approximate time
constants:
Set value (examples):
Resulting time constant:
1:
80 sec
2:
160 sec
5:
~ 7 min
10:
~ 14 min
20:
~ 25 min
50:
~ 1 hour
100:
~ 2 hours
200:
~ 4 hours
250:
~ 5.5 hours
Duct / room temp.
Dead zone (ID no.
11009)
Heating
°
C
Cooling
Actual
Dampened
The setting of 'Accum. filter' prevents unexpected changes between
heating and cooling or changes between heating and passive cooling.
MENU > Settings > Application
Frost pr. T (frost protection temp.)
1x093
Circuit
Setting range
Factory setting
All
*
*
Set the desired flow temperature at temperature sensor S3 to protect the
system against frost (at heating cut-out, total stop etc.).
When the temperature at S3 gets lower than the setting, the motorized
control valve opens gradually.
* See Appendix “Parameter ID overview”
The frost protection temperature can also be set in your favorite
display when the mode selector is in frost protection mode.