Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Temp. monitor
Upper difference
1x147
Circuit
Setting range
Factory setting
All
*
*
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay'.
* See Appendix “Parameter ID overview”
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
Flow / duct temp. °C
Upper difference (set
value)
Desired flow / duct
temp.
Time
MENU > Alarm > Temp. monitor
Lower difference
1x148
Circuit
Setting range
Factory setting
All
*
*
The alarm is activated if the actual flow / duct temperature decreases more
than the set difference (acceptable temperature difference below the desired
flow / duct temperature). See also 'Delay'.
* See Appendix “Parameter ID overview”
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets below the acceptable difference.
Flow / duct temp. °C
Lower difference (set
value)
Desired flow / duct
temp.
Time
MENU > Alarm > Temp. monitor
Delay
1x149
Circuit
Setting range
Factory setting
All
*
*
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in minutes), the alarm function
is activated.
* See Appendix “Parameter ID overview”
Value:
The alarm function will be activated if the alarm
condition remains after the set delay.
Temp.
Flow temp.
Alarm limit
Time
Delay
MENU > Alarm > Temp. monitor
Lowest temp.
1x150
Circuit
Setting range
Factory setting
All
*
*
The alarm function will not be activated if the desired flow / duct
temperature is lower than the set value.
* See Appendix “Parameter ID overview”
If the cause of the alarm disappears, the alarm indication and output
also disappear.