Installation Guide
ECL Comfort 210 / 310, application A214 / A314
Combination of two compensation temperature limit points:
Compensation 1 and 2 can be combined to give a compensation at
2 different compensation temperatures. This can for instance be
used to avoid a too big difference between the indoor and outdoor
temperatures.
The example below shows that below Comp. 1 and above Comp.
2, the desired flow / duct temperature will be increased, but with
different values.
Example :
Comp. 1 value is set to 21 °C and Comp. 2 value is set to 25 °C.
'Infl. min.' for Comp. 1 is set to 2.5 and 'Infl. max.' for Comp. 1 is
set to 0.0.
'Infl. min.' for Comp. 2 is set to 0.0 and 'Infl. max.' for Comp. 2 is
set to 1.5.
The desired flow / duct temperature is kept on a constant level
as long as the compensation temperature is between 21 and 25
°C, but the desired flow / duct temperature will rise if the the
compensation temperature gets above 25 °C or below 21 °C.
Example 1:
Influence
°C
+
-
Temp. Sx
Comp. 1
Comp. 2
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
129