Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A214.2 example b
Heating of a swimming pool, constant water temperature control
S 1
D
a
n
fo
s
s
8
7
H
2
1
1
9
.1
1
ECL 210 / 310
M1
A1
F1
S 3
S 5
S 4
Sensor advice:
Sensor S3 and S4 must be connected. If not, the pump (F1) stops and motorized control valve (M1) closes.
Navigation:
ID no.:
Recommended
setting:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
11676
5 °C
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
11656
5 °C
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
0
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
1
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
0
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
1
Other settings:
Fan cut-in delay — MENU \ Settings \ Fan / acc. control
11086
0
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK
29