Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Alarm > Frost thermostat
Alarm value
1x616
Circuit
Setting range
Factory setting
All
*
*
A frost thermostat can be connected to the frost thermostat sensor input.
When the temperature, measured by the frost thermostat, gets below the set
value, the S7 input will be activated.
The frost alarm can be activated when the contacts in the frost thermostat
open or close.
* See Appendix “Parameter ID overview”
0:
The frost alarm is activated when the contacts in the
frost thermostat close.
1:
The frost alarm is activated when the contacts in the
frost thermostat open.
An activated frost alarm opens the control valve fully, closes the
damper, starts the circulation pump and stops the fan.
'Alarm value' = 0:
An active frost alarm is indicated by a
in the display and as OFF
in favorite display no. 3.
‘Alarm value' = 1:
An active frost alarm is indicated by a
in the display and as ON in
favorite display no. 3.
See also 'Alarm time-out', parameter 1x617.
MENU > Alarm > Air quality
MENU > Alarm > Frost thermostat
MENU > Alarm > Heat recovery
MENU > Alarm > Inlet pressure
MENU > Alarm > Outlet pressure
Alarm time-out
1x617
Circuit
Setting range
Factory setting
All
*
*
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.
* See Appendix “Parameter ID overview”
Value:
Set the alarm time-out
MENU > Alarm > Fire safety
Alarm value
1x636
Circuit
Setting range
Factory setting
All
*
*
A fire thermostat can be connected to the S8 input. When the temperature,
measured by the fire thermostat, gets above the set value, the S8 input will
be activated.
The fire alarm can be activated when the contacts in the fire thermostat
open or close.
* See Appendix “Parameter ID overview”
0:
The fire alarm is activated when the contacts in the fire
thermostat close.
1:
The fire alarm is activated when the contacts in the fire
thermostat open.
An active fire alarm is indicated by a
in the display.
S8 input status:
MENU > Common controller > System > Raw input overview > S8:
0 = Input activated. 1 = input not activated
See also 'Alarm time-out', parameter 1x637.