Installation Guide
ECL Comfort 210 / 310, application A214 / A314
ID
Parameter Name
A214.x
A314.x
Setting range
Factory
Unit
Own settings
11656
Alarm value
2, 3, 4, 5
1, 2, 3, 4, 5, 6, 7, 9
-20 ... 20
6
°C
-||-
6
-20 ... 20
-20
°C
11676
Alarm value
1
-20 ... 20
2
°C
-||-
2, 3, 4, 5, 6
1, 2, 3, 4, 5, 6, 7, 9
-20 ... 20
-20
°C
12140
Comp. T select
4, 5, 6, 7, 9
S1 ; S2 ; S3 ; S4 ;
S5 ; S6 ; S7 ; S8 ;
S9 ; S10 ; S11 ; S12
; S13 ; S14 ; S15 ;
S16
S1
12165
V out max.
1, 2, 4, 5, 6, 7, 9
0 ... 100
100
%
12167
V out min.
1, 2, 4, 5, 6, 7
0 ... 100
0
%
-||-
9
0 ... 100
20
%
12168
Max. Pressure
4, 6
0 ... 1999
400
pascal
12169
Min. Pressure
4, 6
0 ... 1999
50
pascal
12171
Reverse out
1, 2
OFF ; ON
ON
12174
Motor pr.
4, 5
1, 2
OFF, 10 ... 59
OFF
Min
12184
Xp
4, 5
1, 2, 5, 6, 7
5 ... 250
80
K
-||-
4
5 ... 250
100
K
-||-
9
5 ... 250
60
K
12185
Tn
4, 5
1, 2, 5, 6, 7
1 ... 999
30
Sec
-||-
4
1 ... 999
90
Sec
-||-
9
1 ... 999
20
Sec
12186
M run
4, 5
5 ... 250
30
Sec
12187
Nz
4, 5
1, 2
1 ... 9
3
K
-||-
4, 5, 6, 7
1 ... 9
1
K
-||-
9
1 ... 9
2
K
12189
Min. act. time
4, 5
2 ... 50
3
12368
1. step level
9
5 ... 95
80
%
12369
2. step level
9
5 ... 95
85
%
12390
Clear alarm
4, 5, 6, 7, 9
OFF ; ON
OFF
12615
Alarm low
4, 5, 6, 7
0 ... 100
40
%
12617
Alarm time-out
4, 5, 6, 7
0 ... 99
30
Min
13111
Limit
5, 7
0 ... 1999
900
ppm
-||-
9
0 ... 1999
500
ppm
13113
Filter constant
4
1 ... 250
40
-||-
5, 6, 7, 9
1 ... 250
20
13165
V out max.
4, 5, 6, 7, 9
0 ... 100
100
%
13167
V out min.
4, 5, 6, 7
0 ... 100
0
%
-||-
9
0 ... 90
30
%
13184
Xp
4, 5, 6, 7
5 ... 250
80
-||-
9
5 ... 250
60
13185
Tn
4, 5, 6, 7, 9
1 ... 999
30
Sec
206
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy