Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Application
ECA addr. (ECA address, choice of Remote Control Unit)
1x010
Circuit
Setting range
Factory setting
All
*
*
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
* See Appendix “Parameter ID overview”
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
The Remote Control Unit must be set accordingly (A or B).
MENU > Settings > Application
MENU > Settings > Optimization
Total stop
1x021
Circuit
Setting range
Factory setting
All
*
*
Setting the 'Total stop' to OFF or ON gives different results, depending on the
actual application (subtype). The conditions, among others, are:
- Room temperature controlled applications
- Controllers mode
- Desired "Fan function" (ID 11137)
* See Appendix “Parameter ID overview”
No total stop
Heating applications in general:
Saving mode:
The desired flow / duct
temperature is reduced
according to desired duct /
room temperature.
OFF:
Cooling applications in general:
Saving mode:
The cooling is stopped.
ON:
Total stop
Heating applications in general:
Saving mode:
The desired flow / duct
temperature is reduced to
the Frost protection value.
Cooling applications in general:
Saving mode:
The cooling is stopped.
The examples below are related to heating applications:
Desired flow temp. °C
Total stop = ON
‘Frost pr.’
Time
Desired flow temp. °C
Total stop = OFF
‘Frost pr.’
Time
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.