Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A314.6 example c
Ventilation system with heating, cooling and room temperature control. Analog controlled speed of fans in relation to pressures. Analog
controlled valve (M2) for heat recovery by means of a Fluid battery.
8
7
H
1
4
6
9
.1
0
D
a
n
fo
s
s
S 1
S
2
A
1
X
4
P
2
ECL 310
+ ECA 32
S
10
S
13
S 14
X
3
M
1
S
5
S
6
S
7
S
10
S
9
F1 / V2
S
12
S 3
S
8
S
8
S
4
S
9
F1 / V3
M
3
S
11
X
5
P
7
M
2
A
Sensor advice:
Sensor S3 must be connected. If not, the fan F1 stops and motorized control valve M1 closes.
S1, S13 and S14 must be connected in order to calculate the recovery efficiency.
Navigation:
ID no.: Recommended
setting:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
11676
5 °C
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
11656
5 °C
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
0
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
1
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
0
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
1