5.7 Compensation 2
This extra compensation temperature limit setting makes it possible
to change the desired flow / duct temperature in relation to a
second temperature limitation point. The measured compensation
temperature is the same as in section "Compensation 1".
In the parameter descriptions "Sx"is used for the compensation
temperature.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Compensation 2
Limit (compensation temp., 2. point)
1x064
Circuit
Setting range
Factory setting
All
*
*
Set the compensation temperature limit point 2.
* See Appendix “Parameter ID overview”
When the compensation temperature measured by Sx falls below
or gets higher than the set value, the controller automatically
changes the desired flow / duct temperature. The influence is set
in 'Infl. - max.' and 'Infl. - min.'.
Influence
°
C
+
-
Temp. Sx
Compensation 2
MENU > Settings > Compensation 2
Adapt. time (adaptation time)
1x065
Circuit
Setting range
Factory setting
All
*
*
Controls how fast the compensation temperature influences the desired
flow / duct temperature.
* See Appendix “Parameter ID overview”
OFF:
The control function is not influenced by the ‘Adapt.
time’.
Minor
value:
The desired flow / duct temperature is adapted quickly.
Major
value:
The desired flow / duct temperature is adapted slowly.
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.