Function diagram "Fan function", heating / cooling applications:
8
7
H
1
4
9
4
.1
0
D
a
n
fo
s
s
X
#
5 #
# 3 #
#
4 #
# 2 #
# 1 #
X
=
Time
# 1 #
=
Cooling mode
# 2 #
=
Heating mode
# 3 #
=
Dead zone Dz ( ID 11009)
# 4 #
=
Fan function (ID 11137) = ON
# 5 #
=
Fan function (ID 11137) = OFF
MENU > Settings > Application
Stop at T out
1x038
Circuit
Setting range
Factory setting
All
*
*
When the outdoor temperature gets higher than set limit, the related
function is enabled.
* See Appendix “Parameter ID overview”
Value:
Limit for outdoor temperature dependent
functionality.
OFF:
The 'Stop at T out' function is not active.
MENU > Settings > Application
MENU > Settings > Fan / acc. control
P frost T (circulation pump, frost protection temp.)
1x077
Circuit
Setting range
Factory setting
All
*
*
Frost protection, based on the outdoor temperature.
When the outdoor temperature gets below the set temperature value in ‘P
frost T’, the controller automatically switches ON the circulation pump (for
example P1 or X3) to protect the system.
* See Appendix “Parameter ID overview”
OFF:
No frost protection.
Value:
Circulation pump is ON when the outdoor temperature
is below the set value.
Under normal conditions, your system is not frost protected if your
setting is below 0 °C or OFF.
For water-based systems, a setting of 2 °C is recommended.
If the outdoor temperature sensor is not connected and the factory
setting has not been changed to 'OFF', the circulation pump is always
ON.