Installation Guide
ECL Comfort 210 / 310, application A214 / A314
MENU > Settings > Control par.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Motor pr. (motor protection)
1x174
Circuit
Setting range
Factory setting
All
*
*
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
* See Appendix “Parameter ID overview”
OFF:
Motor protection is not activated.
Value:
Motor protection is activated after the set activation
delay in minutes.
Recommended for duct systems with variable load.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Xp (proportional band)
1x184
Circuit
Setting range
Factory setting
All
*
*
* See Appendix “Parameter ID overview”
Set the proportional band. A higher value will result in a stable but
slow control of the flow / duct temperature.
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Tn (integration time constant)
1x185
Circuit
Setting range
Factory setting
All
*
*
* See Appendix “Parameter ID overview”
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.