Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A214.1 example d
Cooling system with constant flow temperature control
S 3
M2
F1
S 1
D
a
n
fo
s
s
8
7
H
2
1
1
6
.1
1
ECL 210 / 310
A1
Setting advice:
Set desired room temperature, for example 1 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set ‘Fan cut-in delay’ (ID no. 11086 — ‘Settings’, ‘Fan / acc. control’) to 0 seconds.
A214.1 example e
Cooling system in ceiling and constant room temperature control in for example a wine cellar
S 1
D
a
n
fo
s
s
8
7
H
2
1
1
7
.1
2
ECL 210 / 310
A1
S 3
S 4
F1
M2
Setting advice:
Set desired room temperature, for example 14 °C.
Set desired balance temperature, for example 10 °C.
If a room temperature sensor is not connected, the desired flow temperature at S3 will correspond to the desired room temperature.
Set ‘Fan cut-in delay’ (ID no. 11086 — ‘Settings’, ‘Fan / acc. control’) to 0 seconds.
Danfoss District Energy
VI.GU.A2.02
DEN-SMT/DK