Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A314.3 example a
Ventilation system with heating and constant room temperature control. Analog controlled fan speed (V1) based on outdoor wind speed.
ECL 310
S 3
P 2
S 5
M1
S 6
X3
S 7
F1 / V1
S 8
S 8
S 8
S 1
D
a
n
fo
s
s
8
7
H
2
1
3
1
.1
2
A1
S10
+ ECA 32
S 4
S 2
Setting advice:
Set desired room temperature, for example 20 °C.
Set desired balance temperature, for example 35 °C.
If a room temperature sensor is not connected, the desired duct temperature at S3 will correspond to the desired room temperature.
Navigation:
ID no.: Recommended
setting:
Special settings for sensors / thermostats used as frost protection:
S6* frost temperature sensor — MENU \ Alarm \ Frost T \ Alarm value
11676
5 °C
S5 return temperature sensor — MENU \ Alarm \ Limit T frost \ Alarm value
11656
5 °C
Closing contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
0
Opening contact of the S7* frost thermostat — MENU \ Alarm \ Frost thermostat \ Alarm value
11616
1
* both frost protection methods, by means of S6 and / or S7, can be used
Special settings for thermostats used as fire alarm:
Closing contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
0
Opening contact of the S8 fire thermostat — MENU \ Alarm \ Fire safety \ Alarm value
11636
1
42
DEN-SMT/DK
VI.GU.A2.02
Danfoss District Energy