Installation Guide
ECL Comfort 210 / 310, application A214 / A314
A314.4, A314.5, A314.6 and A314.7:
Efficiency calculation:
( Entry duct - Outdoor )
x 100
( Exit duct - Outdoor )
= %
Example:
Outdoor (S1)
=
7 °C
Entry duct (S13) = 16 °C
Exit duct (S14)
= 24 °C
( 16 - 7 )
x
100
( 24 - 7 )
= 53 %
A314.4, A314.5, A314.6 and A314.7:
Circuit 1's overview display shows output status for M1.
An approximate %-value for M1's position is also indicated in order
to follow the control procedure.
The controller is pre-programmed with factory settings that are shown
in the ‘Parameter ID overview’ appendix.