19
MYDENS
COSMOGAS
5 - INSTALLATION
5.10 - Safety valve
The appliance is protected against overpressures by a
safety valve calibrated to 3 bar (detail “7” Figure 1). The
safety valve drain is conveyed to pipe “F” (Figure 13)
which must be then taken to the anti-odour siphon (detail
“G” Figure 14). This drain with a siphon is used to prevent
overpressures if the valve is opened, and it allows the user
to check intervention.The anti-odour siphon “G” (Figura 14)
is provided on request.
a
WARNING!!! If the safety valve is not connected
to the drain, whenever the valve intervenes, it could
cause damage to persons, animals or objects.
F
G
020002.01.028
min10 mm
max 30 mm
Figure 14
5.11 - Hydraulic and gas connections,
and mounting of the bottom cover
E
B
A
F
G
C
D
H
020002.01.004
Figure 15
A = heating supply
Ø 18 in the 15 and 24 models
Ø 22 in the 34 model
B = domestic hot water Ø 14
(absent in the “B” and ”C” models)
C = gas inlet valve
(EN 331 type-approved)
D = 1/2" domestic cold water inlet valve
E = gas Ø18
F = domestic cold water Ø14
G = heating return
Ø 18 in the 15 and 24 models
Ø 22 in the 34 model
Once the hydraulic and gas connections have been made,
proceed with assembly of the bottom cover “H” as indicated
in Figure 15.
l
The accessories, in some models, could be not
supplied with the appliance.