90
MYDENS
COSMOGAS
9 - TECHNICAL DATA
MYDENS TECHNICAL DATA
UM
15
24
34
Type (Type of flue exhaust/air intake)
B23; B23P; C13; C33; C43; C53; C63; C83; C93
Category
II2H3P
II2H3P
II2H3P
EU type approval certificate (PIN)
0476CQ1097
0476CQ1097
0476CQ1097
Range Rated Boiler
APPROVED
APPROVED
APPROVED
Central heating max. heat input “Qn” PCI (PCS)
kW
14,0 (15,5)
25,5 (28,3)
32,0 (35,5)
Domestic hot water max. heat input “Qnw” PCI (PCS)
kW
/
25,5 (28,3)
32,0 (35,5)
Heating minimum heat input PCI (PCS)
kW
3,2 (3,6)
3,2 (3,6)
6,0 (6,7)
Domestic hot water minimum heat input PCI (PCS)
kW
/
3,2 (3,6)
6,0 (6,7)
Central heating max useful output power (80/60) “Pn”
kW
13,6
24,8
30,9
Efficiency at 100% load (80/60) PCI (PCS)
%
96,5 (86,9)
97,3 (87,6)
96,8 (87,2)
Minimum useful output power (80/60)
kW
3,02
3,02
5,75
Efficiency at minimum useful output power (80/60) PCI (PCS)
%
94,5 (85,1)
94,5 (85,1)
95,8 (86,3)
Central heating max. useful output power (50/30)
kW
14,9
27,0
33,5
Efficiency at central heating max. useful output power (50/30) PCI (PCS)
%
106,5 (96,0)
105,7 (95,2)
104,7 (94,3)
Min. useful output power (50/30)
kW
3,3
3,3
6,14
Efficiency at min. useful output power (50/30) PCI (PCS)
%
103,0 (92,8)
103,0 (92,8)
102,4 (92,3)
Efficiency at 30% of the load PCI (PCS)
%
107,5 (96,8)
108,5 (97,7)
107,0 (96,3)
Losses at the chimney, burner ON (80/60)
%
1,5
1,5
1,5
Losses at the chimney, burner OFF
%
0,1
0,1
0,1
Losses at the casing, burner ON (80/60)
%
0,5
0,5
0,5
Losses at the casing, burner OFF
%
0,1
0,1
0,1
Gas flow rate
G20
m3/h
1,48
2,7
3,38
G31
kg/h
1,09
1,98
2,48
Gas supply pressure
G20
mbar
20
20
20
G31
mbar
37
37
37
Gas supply minimum pressure
G20
mbar
17
17
17
G31
mbar
25
25
25
Gas supply maximum pressure
G20
mbar
25
25
25
G31
mbar
45
45
45
Primary heat exchanger water content
l
2,9
2,9
2,9
Secondary heat exchanger water content
l
/
0,5
0,5
Domestic hot water useful output power
kW
/
27
33,5
DHW minimum flow rate
l/min
/
2
2
Instantaneous DHW production (dt 30°C)
l/min
/
12,9
16,0
Instantaneous DHW adjustment range
°C
/
40-60
40-60
DHW adjustment range with tank
°C
40-70
40-70
40-70
Design temperature
°C
95
95
95
Maximum central heating temperature
°C
80
80
80
Minimum central heating temperature
°C
20
20
20
Содержание Adveco MYDENS 15B
Страница 10: ...10 MYDENS COSMOGAS 4 OPERATION Figure 3 MYDENS 24P MYDENS 34P Figure 4 MYDENS 15B MYDENS 24B MYDENS 34B...
Страница 88: ...88 MYDENS COSMOGAS 8 MAINTENANCE 8 26 Wiring diagram Figure 77...
Страница 96: ...COSMOGAS s r l Via L da Vinci 16 47014 Meldola FC Italia info cosmogas com www cosmogas com...