73
MYDENS
COSMOGAS
7 - USE
7.17.3 - Diagnostics: Alarms “AttE”
Alarm
Alarm description
Checks
Solutions
AttE 200 System with appliances in a cascade.
The cascade management system
has lost the connection with one of the
appliances.
One of the appliances in the cascade is off.
Switch-on the appliance which is turned off,
only after the cause of its shutdown has been
resolved.
The communication BUS between the
appliances (A-Link) is interrupted in one or
more points.
Restore the BUS communication between the
appliances.
Parameters
4184
and/or
4147
are
not set according to the rules in section 5.15.
Set the perameters
4184
and/or
4147
correctly, according to the rules in
section 5.15.
the S4 switches,mentioned in section 5.15,
are not positioned as described in that
section.
Position the S4 switches as described in
section 5.15.
AttE 201 Protective anode active (N/A)
Replace the control board
AttE 202 Connected appliance recognition error
(N/A)
Replace the control board
AttE 203 Communication lost with appliance
connected in cascade (N/A)
Replace the control board
AttE 204 Outdoor temperature sensor error
(contact open or shortcircuited)
Check the electrical resistance of the sensor; If the electrical resistance does not match,
replace it.
If the electric circuit is damaged, repair it.
Where neither of the two previous cases
apply, replace the control board.
Check that it has been connected correctly.
Restore the correct connection.
AttE 205 Cascade temperature sensor error
(contact open or shortcircuited)
Check the electrical resistance of the sensor; If the electrical resistance does not match,
replace it.
If the electric circuit is damaged, repair it.
Where neither of the two previous cases
apply, replace the control board.
Check that it has been connected correctly.
Restore the correct connection.
AttE 206 Cascade temperature sensor error
(contact open or shortcircuited) (N/A)
Replace the control board