28
MYDENS
COSMOGAS
5 - INSTALLATION
5.17 - Flue exhaust and air intake ducts
a
WARNING!!! To connect the flue exhaust and air
intake, the relevant national and local regulations
must be respected.
a
WARNING!!! The flue gas from this appliance
can reach 90°C in certain conditions. Therefore, use
pipes in plastic that can resist high temperatures.
a
WARNING!!! This appliance is a “condensing”
appliance. Use AISI 316L stainless steel materials or
polypropylene plastic materials to make the flue gas
so as to prevent corrosion due to the acidity of the
condensate.
l
Please remember that appliances of this type
must have exhaust and intake ducts supplied by the
manufacturer of the appliance itself. Other types of pipes,
if used, must be type-approved for this intended use.
l
The types of exhaust for which the appliance is
approved are given in the technical features table at
the end of the manual under the “type” heading and on
the data plate on the appliance, also under the “type”
heading.
The symbols used to define the type of exhaust are given
below:
- B23 and B23P, separated with intake in room and exhaust
through wall or roof;
a
WARNING!!! If the appliance is installed
with a B23 or B23P exhaust, it will take in air for
combustion from the surrounding environment.
Therefore, all precautions must be taken regarding
ventilation of the rooms as prescribed by the
national and/or local regulations.
- C13, coaxial in vertical wall;
- C33, coaxial at the roof;
- C43, separated with exhaust in flue, combined with intake
in common channel;
a
WARNING!!! The appliances installed in type C43
must only be connected to natural-draught flues.
- C53, separated with exhaust on roof and intake on wall, or
in two potentially different pressure points;
a
WARNING!!! With installation type C53, the flue
exhaust and air intake terminals cannot be installed
on opposite walls of the building.
- C63, the appliance can be fitted to type-approved exhaust
and intake pipes made by other brands;
Figure 25