ID-FLX Lite Global Guide
28
Settings DIRECT = module works in GPRS network and enables connection via AirGate to LiteEdit and
WebSupervisor as well as sending SMS alarms.
Settings MODEM = module works as standard GSM modem enabling CSD (Circuit Switch Data) connection to
controller with LiteEdit or other ComAp PC SW and sending alarm SMSes.
Module is usually used for connection to remote monitoring and controlling system WebSupervisor
or to PC tools. Module is capable of sending alarm SMS based on settings in
SMS / Email setpoint group.
IMPORTANT: Any manipulation with plug-in module shall be done with disconnected power
supply to both controller and module. Power supply shall be switched on also is same time to both
module and controller. Fail to follow these instructions (power supply active only in controller or
only in module) can lead to module or controller failure!
IMPORTANT: GPRS and CSD connection is not suitable for firmware update process, kindly used
wired connection instead like RS232, USB, RS485 or Ethernet via IB-Lite!
Note:
Quick guide how to start using this module is in chapter Remote Communication – Short guide how to
start using IL-NT GPRS module or on
Note:
Use of this plug-in brings WSUP Locate function. This function allows monitoring actual engine position
based on GSM signal information. The position is automatically updated and stored in WSV history. You can
track the position of the engine in WebSupervisor even in history.
Note:
Unlike GPS system, the function works indoor or wherever the GSM signal is. Precision of localization is
not as precise as with GPS and depends on density of operator’s GSM / BTS tower around the controller.
4.6 Remote modules
Remote modules allow monitoring and displaying of values and states away from main controller.
4.6.1 IL-NT RD (SW)
IL-NT-RD is remote display software for a controller. Remote display provides the same control and monitoring
functions as controller itself. Remote display for InteliDrive controllers uses standard ID-Lite controller with
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...