ID-FLX Lite Global Guide
177
Setpoint group
Sensors Spec
Related FW
2.5.0
Range [units]
[Always / Running / OFF]
Default value
OFF
-
Step
-
Comm object
14283
Related applications
Description
Setting of Counter 1 and Counter 2 mode:
Always
Corresponding counter counts pulses all time.
Running
Corresponding counter counts pulses only when engine is running.
OFF
Corresponding counter does not count pulses. Default settings.
Note:
The Total 1 and Total 2 values are visible in LiteEdit – Values – Statistics.
The Total 1 and Total 2 values disappear from controller screen when both Counter modes 1 and 2 are
switched OFF otherwise there is new screen between existing Statistics and Alarm list.
Counter mode 1, Counter mode 2
Group: AIO module
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13650
Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO1 lev1
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
-100 .. 10000 [-]
Default value
0
-
Step
1
Comm object
13651
Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO2 lev1
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...