ID-FLX Lite Global Guide
200
Related FW
2.5.0
Related applications
Comm object
24
Description
Closed relay energizes the starter of engine.
The relay opens if:
The strating speed is reached or
Maximum time of cranking is exceeded or
Request to stop comes up
Starter
Related FW
2.5.0
Related applications
Comm object
22
Description
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
Cooled engine is stopped or
In pause between repeated starts
Fuel solenoid
Related FW
2.5.0
Related applications
Comm object
23
Description
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer; it stays active until all symptoms say the
engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure <
Note:
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact
the Stop solenoid can still be active (in that case it is deactivated before cranking).
Note:
In case when stop time period is lower than "stop engine detected" + 10 s, stop time period is
extended to this value due to safety reason. (stop engine detected = RPM<2, OilP not detected, D+ not
active)
Stop solenoid
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...