ID-FLX Lite Global Guide
69
Input
Analog input
CU: AI1-AI9
AIO: AI1-AI4
Binary output
Load Switch
Setpoints
Load limit
Load CMP Input = AI1
Load CMP On = 90
Load CMP Off = 80
Engine load limitation with On/Off output
Purpose: Protect the engine against overload by reducing (switching On/Off) the load.
Description: CMPH (Comparator with Hysteresis) detect the RPM decrease below the Down limit, activates
the Binary output Load switch that reduces (slow down feeder) the load. There are expected corresponding
droop characteristics on the engine.
Input
RPM from pickup (or ECU)
Binary output
Load Switch
Setpoints
Load limit
Load CMP Input = RPM
Load CMP On = e.g. 2000
Load CMP Off = e.g. 2200
Speed switch
Purpose: Switch on/off some device depends on RPM level.
Description: Depends on setpoint settings the CMPH (Comparator with Hysteresis) activates/deactivates the
Binary output Load switch that switch off some device when RPM is below adjusted limit.
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...