ID-FLX Lite Global Guide
180
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
5
-
Step
1
Comm object
13659
Related applications
Description
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
Note:
Plug-in analog inputs protection alarms can be configured following way.
AnlInAIO2 del
Setpoint group
AIO module
Related FW
2.5.0
Range [units]
0 .. 180 [s]
Default value
5
-
Step
1
Comm object
13660
Related applications
Description
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
Note:
Plug-in analog inputs protection alarms can be configured following way.
AnlInAIO3 del
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...