ID-FLX Lite Global Guide
36
5 Controller setup
5.4 Remote modules - CAN bus connection
5.8 How to select the engine mode?
5.9 How to view measured data?
5.10 How to view and edit setpoints?
5.11 How to find active alarms?
5.12 How to list History records?
5.13 MEASUREMENT screens description
5.14 Display screens and pages structure
5.1 Analog inputs
On the ID-Lite controller nine analog inputs are available. See the two tables here bellow with specific
characteristics.
All here mentioned properties can be modified by LiteEdit PC tool only, in the window Modify
.
5.1.1 Table of controller analog inputs
Input
Range
Default use
Configurability
of default use
AIN1
0 – 2.4 kΩ
Oil pressure
NO
AIN2
0 – 2.4 kΩ
Engine temperature
YES
AIN3
0 – 2.4 kΩ
Fuel level
YES
AIN4
0 – 40 V
Not used - free
YES
AIN5
0 – 40 V
Not used - free
YES
AIN6
0 – 10 V
Not used - free
YES
AIN7
0 – 10 V
Not used - free
YES
AIN8
0 – 10 V
Not used - free
YES
AIN9
0 – 10 V
Not used - free
YES
Note:
The nominal range of Analog inputs measuring resistivity is 0 – 2.4 kΩ, nevertheless the input is able to
measure up to 15 kΩ, but with lower precision.
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...