ID-FLX Lite Global Guide
119
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
IDLE, NOMINAL [-]
Default value
-
Step
-
Comm object
10046
Related applications
Description
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state.
IDLE
Cooling is executed at Idle speed.
NOMINAL
Cooling is executed at Nominal speed. Default state.
Note:
Binary output IDLE/NOMINAL must be configured and connected to speed governor. Engine Idle
speed must be adjusted on speed governor.
Cooling speed
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
30
-
Step
1
Comm object
8258
Related applications
Description
Run time of the unloaded engine to cool the engine before stop.
Cooling time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
180
-
Step
1
Comm object
8662
Related applications
Description
Run time of engine after cooling pump.
is closed when the engine starts and
opens AfterCool time delayed after engine stops.
AfterCool time
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...