ID-FLX Lite Global Guide
136
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
80
YES
Step
1
Comm object
11852
Related applications
Description
Regulator requested value.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
LoadRequest 1
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
-10000 .. +10000 [-]
Default value
80
YES
Step
1
Comm object
11853
Related applications
Description
Regulator requested value when
is active.
Value of this Setpoint should be given in value of quantity without decimal point.
Example:
When AIN is configured in such way that Load limit set on 5 V to maintain the value
8.54 bar, then the value inserted to this Setpoint is 854.
Load request 2
Setpoint group
ATT settings
Related FW
2.5.0
Range [units]
1 .. 10000 [1/s]
Default value
1000
YES
Step
1
Comm object
11854
Related applications
Description
Ramp when is switched between
and
.
LoadReq Ramp
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...