ID-FLX Lite Global Guide
148
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U16]
Default value
10
-
Step
1
Comm object
13369
Related applications
Description
High ShutDown limit level for AIN4.
AIN4 HighSd
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 3600 [s]
Default value
10
-
Step
1
Comm object
13370
Related applications
Description
High level protection delay for Wrn and Sd of AIN4.
Note:
Analog input 4 is fully configurable and it is voltage type of input with range 0-40 V.
AIN4 HighDel
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000[U17]
Default value
20
-
Step
1
Comm object
9274
Related applications
Description
Warning limit level for AIN5.
AIN5 Level 1
Setpoint group
Engine protection
Related FW
2.5.0
Range [units]
0 .. 10000 [U17]
Default value
10
-
Step
1
Comm object
9275
Related applications
Description
Shutdown limit level for AIN5.
AIN5 Level 2
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...