ID-FLX Lite Global Guide
85
Note:
It is possible to create multiple controller connection through RS485. Be aware of controller address
collision. Manage address setting for each controller in
Note:
ComAp recommends using galvanicaly separated cable.
8.2 Remote connection
8.2.1 Internet connection
ID-Lite controllers can be monitored from PC tools as LiteEdit or InteliMonitor over the Internet using
InteliBridge-NT connected to the controller via IL-NT RS232-485 port, via optional IB-Lite plug-in module or via
IL-NT GPRS for cellular internet network,
see Group: Communication settings on page 106
.
8.2.2 AirGate connection
ID-Lite controllers can be monitored from PC tools as LiteEdit or InteliMonitor via AirGate. AirGate technology is
for easy plug and play wireless communication. Common SIM card with GPRS service is suitable for this
system. It overcomes problems with special SIM card (fixed and public IP) necessity, with firewalls and difficult
communication settings. For AirGate connection is possible to use IB-NT, IB-Lite or IL-NT GPRS modules. For
setting
see Group: Communication settings on page 106
8.2.3 Modem connection
PC can be connected to the controller also remotely via modems. Either an analog, GSM, ISDN or 3G modem
must be connected to the RS232 interface,
see Group: Communication settings on page 106
: COM1 Mode
has to be set to MODEM.
Note:
RF modem communication is also possible between controller and remote display.
Note:
In case of controller and remote display RF modem should be connected with serial cable with only three
connected pins Rx, Tx and GND. In other case could be blocked communication between modem and
controller.
8.3 Modbus connection
Modbus protocol was implemented into the controllers to allow design of own supervision software offering
customer or to use ComAp SCADA software.
To learn more about Modbus interface see the training videos on
and
.
8.3.1 Modbus step by step
Use LiteEdit: Controller->Generate Cfg image->Modbus registers command to get registers list.
9600 bps, 8 data bits, 1 stop bit, no parity
Transfer mode RTU
Function 3 (Read Multiply Registers) max length of block is 127 registers
Function 6 (Write Single Register)
Function 16 (Write Multiply Registers) max 16 registers
The response to an incoming message is sent with minimum 4.096 ms delay after message reception
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...