ID-FLX Lite Global Guide
115
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
2
-
Step
1
Comm object
8394
Related applications
Description
Time of the PRESTART output closed prior to the engine start – i.e. before the binary outputs Fuel solenoid
and Starter are closed and opens when Starting RPM speed is reached. Set to zero if you want to leave the
output PRESTART opened.
Prestart time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 600 [s]
Default value
0
-
Step
1
Comm object
11836
Related applications
N/A
Description
This setpoint is used for setting of timer for deactivation of
.
Preglow time
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
-600 ..
[°C]
Default value
0 °C
-
Step
1 °C
Comm object
15985
Related applications
N/A
Description
Defines the temperature, at which the LBO Preheat activate of the longest time prior to engine start. See
description of
.
PreheatTemp1
Содержание InteliDrive FLX LITE
Страница 19: ...ID FLX Lite Global Guide 19 4 3 Terminal diagram and dimension ...
Страница 21: ...ID FLX Lite Global Guide 21 Example Default analog output curves ...
Страница 22: ...ID FLX Lite Global Guide 22 Example Wiring for Dacon gauges and IL NT AOUT8 ...
Страница 43: ...ID FLX Lite Global Guide 43 When you finish with adjusting the values click OK and Write to controller ...
Страница 44: ...ID FLX Lite Global Guide 44 5 2 Binary inputs and outputs ...
Страница 57: ...ID FLX Lite Global Guide 57 5 14 Display screens and pages structure ...
Страница 83: ...ID FLX Lite Global Guide 83 7 Communication 6 back to Table of contents ...
Страница 92: ...ID FLX Lite Global Guide 92 10 Appendix 10 2 Extension modules 225 6 back to Table of contents ...